10KV Cable Line Phase Sequence Detection

June 5, 2026

Latest company case about 10KV Cable Line Phase Sequence Detection

10KV Cable Line Phase Sequence Detection

Client: State Grid Jinzhai County Power Supply Company

Location: Jinzhai County, Anhui, China

Test Date: May 16, 2024 / Sunny / 28°C

Instrument: TAG-8800 Remote Wireless High Voltage Phase Tester

Service Provider: HKVTest

latest company case about 10KV Cable Line Phase Sequence Detection


Test Method

Phase angles at both ends of each cable line were measured. A phase difference of less than 6 degrees between the same phases indicates consistent phase sequence.

Three 10KV lines were tested against the 110kV Jiangdian Substation as reference.

latest company case about 10KV Cable Line Phase Sequence Detection

Line 1 – Gongyeyuan Line 15:

  • Phase A differences: 5°, 2°, 3°
  • Phase B differences: 3°, 2°, 2°
  • Phase C differences: 2°, 1°, 3°

All within 6 degrees. Result: Phase sequence consistent.

Line 2 – KD18 Line:

  • Phase A differences: 1°, 1°, 2° → consistent
  • Phase B differences: 123°, 125°, 126° → inconsistent
  • Phase C differences: 248°, 133°, 120° → inconsistent

Conclusion: Phase A is correct; Phase B and Phase C are reversed.

Line 3 – Jiangtian Line 16:

  • Phase A differences: 3°, 1°
  • Phase B differences: 3°, 2°
  • Phase C differences: 3°, 1°

All within 6 degrees. Result: Phase sequence consistent.

latest company case about 10KV Cable Line Phase Sequence Detection

Final Conclusion:

HKVTest successfully identified a phase reversal on KD18 Line (B and C phases reversed). The client was able to correct the wiring before energization, preventing a potential short circuit or equipment damage. The other two lines were confirmed correct.